Cooling Towers Model: FBT/IBT
Features Construction Fans Water Distribution Systems Wet Deck Surface Air Inlet Louvers and Drift Eliminators Benefits Electrical Options |
| Model | FBT-30 | FBT-40 | FBT-50 | FBT-65 | FBT-80 | FBT-95 | FBT-115 | FBT-125 | FBT-135 | |
| Cooling Capacity | Tons | 30 | 39 | 50 | 65 | 80 | 95 | 115 | 125 | 135 |
| Fans | No.xhp | 1x3 | 1x5 | 1x3 | 1x7.5 | 1x10 | 1x10 | 1x15 | 1x20 | 1x20 |
| Flow | USgpm | 90 | 117 | 150 | 195 | 240 | 285 | 345 | 375 | 405 |
| Connections | Inches In/Out |
(1) 3 (1) 4 |
(1) 3 (1) 4 |
(1) 4 (1) 6 |
(1) 4 (1) 6 |
(1) 6 (1) 8 |
(1) 6 (1) 8 |
(1) 6 (1) 8 |
(1) 6 (1) 8 |
(1) 6 (1) 8 |
| Dimensions (LxWxH) | Inches | 88x50x80 | 88x50x98 | 135x50x80 | 135x50x80 | 185x50x80 | 185x50x98 | 220x50x80 | 220x50x80 | 220x50x98 |
| Operating weight | lbs. Approx. | 1800 | 1950 | 2850 | 2900 | 3850 | 4100 | 4800 | 4850 | 5200 |
| Shipping weight | lbs. Approx. | 1300 | 1400 | 1800 | 1900 | 2300 | 2600 | 2800 | 2890 | 3100 |
| Notes: |
1. Single cell models, forced draft design. 2. Capacity based on 85ºF leaving water, 78ºF entering wet bulb and 95ºF return water temperature. 3. Tower flow rate based on 3 USgpm/ton. 4. Specifications and dimension are subject to change without notice. |
|||||||||
| Model | IBT-145 | IBT-160 | IBT-175 | IBT-200 | IBT-225 | IBT-250 | IBT-270 | IBT-325 | IBT-365 | |
| Cooling Capacity | Tons | 145 | 160 | 175 | 200 | 225 | 250 | 270 | 325 | 365 |
| Fans | No.xhp | 1x7.5 | 1x10 | 1x10 | 1x15 | 1x15 | 1x20 | 1x20 | 1x20 | 1x25 |
| Flow | USgpm | 435 | 480 | 525 | 600 | 675 | 750 | 810 | 975 | 1095 |
| Connections | Inches In/Out |
(1) 6 (1) 8 |
(1) 6 (1) 8 |
(1) 6 (1) 8 |
(1) 6 (1) 8 |
(1) 6 (1) 8 |
(1) 6 (1) 8 |
(1) 6 (1) 10 |
(1) 8 (1) 10 |
(1) 8 (1) 10 |
| Dimensions (LxWxH) | Inches | 144x103x129 | 144x103x129 | 144x103x145 | 144x103x145 | 144x103x177 | 144x103x177 | 144x103x193 | 144x148x177 | 144x148x193 |
| Operating weight | lbs. Approx. | 7,500 | 7,600 | 8,100 | 8,300 | 10,100 | 10,300 | 11,000 | 13,200 | 14,200 |
| Shipping weight | lbs. Approx. | 4,000 | 4,100 | 4,300 | 4,350 | 5,450 | 5,500 | 5,800 | 6,800 | 7,200 |
| Notes: |
1. Single cell models, induced draft design. 2. Capacity based on 85ºF leaving water, 78ºF entering wet bulb and 95ºF return water temperature. 3. Tower flow rate based on 3 USgpm/ton. 4. Specifications and dimension are subject to change without notice. |
|||||||||
| Model | IBT-290D | IBT-320D | IBT-350D | IBT-400D | IBT-450D | IBT-500D | IBT-540D | IBT-650D | IBT-730D | |
| Cooling Capacity | Tons | 290 | 320 | 350 | 400 | 450 | 500 | 540 | 650 | 730 |
| Fans | No.xhp | 2x7.5 | 2x10 | 2x10 | 2x15 | 2x15 | 2x15 | 2x20 | 2x20 | 2x25 |
| Flow | USgpm | 870 | 960 | 1050 | 1200 | 1350 | 1500 | 1620 | 1950 | 2190 |
| Connections | Inches In/Out |
(2) 6 (2) 8 |
(2) 6 (2) 8 |
(2) 6 (2) 8 |
(2) 6 (2) 8 |
(2) 6 (2) 8 |
(2) 6 (2) 8 |
(2) 6 (2) 10 |
(2) 8 (2) 10 |
(2) 8 (2) 10 |
| Dimensions (LxWxH) | Inches | 144x206x129 | 144x206x129 | 144x206x145 | 144x206x145 | 144x206x177 | 144x206x177 | 144x206x193 | 144x296x177 | 144x296x193 |
| Operating weight | lbs. Approx. | 15,000 | 15,200 | 16,200 | 16,600 | 20,200 | 20,600 | 22,000 | 26,400 | 28,400 |
| Shipping weight | lbs. Approx. | 8,000 | 8,200 | 8,600 | 8,700 | 10,900 | 11,000 | 11,600 | 13,600 | 14,400 |
| Notes: |
1. Dual cell models, induced draft design. 2. Capacity based on 85ºF leaving water, 78ºF entering wet bulb and 95ºF return water temperature. 3. Tower flow rate based on 3 USgpm/ton. 4. Specifications and dimension are subject to change without notice. |
|||||||||